If a PV from a pressure transducer produces a 0 to 20 mA signal and the A/D converter has a range of 2,865 to 16,384, what would be the expected value from the A/D converter if a 9.34 mA PV signal is received from the transducer

ansver
Answers: 3

Other questions on the subject: Engineering

image
Engineering, 04.07.2019 03:10, lauriepdx17
What precautions should you take to prevent injuries when dealing with heavy loads?
Answers: 1
image
Engineering, 04.07.2019 18:10, yasminothman02
An air conditioning system consist of a 5 cm diameter pipe, operating at a pressure of 200 kpa. the air initially enters the pipe at 15°c with a velocity of 20 m/s and relative humidity of 80%. if the heat supply throughout the process is 960 w, determine the relative humidity and the temperature at the outlet