A 230 V, single-phase supply feeds the following loads: (a) incandescent lamps taking a current

of 6 A at unity power factor; (b) fluorescent lamps taking a current of 5 A at 0.75 leading power

factor; (c) a motor taking a current of 7 A at 0.7 lagging power factor. You are required to

correct the power factor to unity.

a) Show how it can be achieved by connecting a parallel reactance to the load

- provide the phasor diagram based on computed branch currents; and the power

triangles before and after power factor correction.

- provide the appropriate kVar rating of reactance, and if it’s a capacitor bank compute

the capacitance or if it’s an reactor (inductor) compute the inductance.

b) If it is proposed to use series reactance to perform power factor correction, show how this

can be achieved and comment on this approach.

d) Verify your answers using Matlab/Simulink

- show the rms currents on the Simulink model

- Plot the instantaneous branch currents and show clearly how the phase angle between

the supply voltage and supply current changes, accordingly

ansver
Answers: 1

Other questions on the subject: Engineering

image
Engineering, 04.07.2019 18:10, niyawilliams23
Asingle-geared blanking press has a stroke of 200 mm and a rated capacity of 320 kn. a cam driven ram is assumed to be capable of delivering the full press load at constant force during the last 15 percent of a constant-velocity stroke. the camshaft has an average speed of 90 rev/min and is geared to the flywheel shaft at a 6: 1 ratio. the total work done is to include an allowance of 16 percent for friction a) estimate the maximum energy fluctuation b) find the rim weight for an effective diameter of 1.2 m and a coefficient of speed fluctuation of 0.10
Answers: 1
image
Engineering, 04.07.2019 18:10, lowkeyqueenk
Apipe with an outside diameter of 15 cm is exposed to an ambient air and surrounding temperature of -20°c. the pipe has an outer surface temperature of 65°c and an emissivity of 0.85. if the rate of heat loss from the pipe surface is 0.95 kw per meter of length, the external convective heat transfer coefficient (h) is: (a) 12.5 w/m"k (b) 18.6 w/mk (c) 23.7 w/mk (d) 27.9 w/mk (e) 33.5 w/mk
Answers: 1
image
Engineering, 04.07.2019 18:20, rhussein6452
Wiy doeres rere okhn a pump whon working betwon the same pressure range?
Answers: 2
image
Engineering, 04.07.2019 19:10, jimena15
10 kg of co2 is initially contained at 400 kpa and 300 k. the gas constant for carbon dioxide is 189 j/lkg k) and has a specific heat ratio, k, of 1.289. isentropic expansion then occurs until the pressure is 200 kpa. a) determine the initial volume of co2 in m. b) determine the final temperature in k. c) determine the work done by the system during the expansion kl.
Answers: 2
You know the right answer?
A 230 V, single-phase supply feeds the following loads: (a) incandescent lamps taking a current

Questions in other subjects:

Konu
Mathematics, 15.10.2019 13:30